ESP
MAG4P
4 Zone ABS Conventional Fire Panel
General Information
Dimensions (mm) 340 x 290 x 100
Maximum Detectors Per Zone 30
Thresholds for Zone Conditions (mA) 0 - 2 (Fault condition)
2 - 6 (Normal condition)
6 - 110 (Fire condition)
Call Points Per Zone Unlimited
Weight (Kg) 2.1Kg (Without Battery)
Warranty (Years) 3
Supply & Power
Supply Voltage (V AC) 230
Power Availability (A) 0.7
Mains Fail Consumption (mA) 50
Standby Supply Up to 12V 7Ah (Battery Calculation Required)
Sounder 1 & 2 24V DC (maximum 300mA fused) Monitored
Inputs & Outputs
Detection Zone End Of Line Custom EoL; MAG-EOL
Fault/Fire Relay Volt free 500mA @ 24V (max load)
Auxiliary Output 24V DC (300mA fused)
Sounder 1 Output 24V DC (max 300mA fused)
Sounder 2 Output 24V DC (max 300mA fused)
Environment
Operating Temperature (°C) -5 to +40
Storage Temperature (°C) -20 to +60
Relative Humidity Resistance (%) 93 (±3) (@40°C)
Standards BS EN 54-4, BS EN 54-2
Any orders below £75 subject to £6.00 carriage
- Stock: 2
- Model: ESPMAG4P
- SKU: ESPMAG4P
- MPN: MAG4P