NIGLON SA23-415
230/400v Type 2/3 Surge Protection Device.
Technical Specifications.
Description Compact 3 + N phase type 2 (or 3)
Network 230/400V 3-Phase
Connection Mode L/N and N/PE
AC system TN
Max. AC Operating Voltage 255 Vac
Temporary Over Voltage [TOV] Characteristics - 5 sec 335 Vac withstand
Temporary Over Voltage [TOV] Characteristics - 120m 440 Vac disconnection
Temporary Over Voltage N/PE [TOV HT] 1200 v/300A/200ms withstand
Residual Current Leakage Current at Uc None
Follow Current None
Nominal discharge current 15 x 8/20 µs impulses 5kA
Max discharge current max. withstand @ 15 x 8/20µs by pole 15kA
Withstand on overvoltages IEEEC62.41.1 10kV
Protection Level CM/DM @ In (8/20µs) and @ 6kV (1.2/50µs) 1.25 kV
Admissible short-circuit current 10000A
Thermal Disconnector Internal
Fuses Fuse type gG-20A*
Installation ground fault breaker Type “S” or delayed
Connection to Network Screw Terminals: 1.5-10mm2 (L/N) or 2.5 -25mm2 (PE)
Mounting Symmetrical rail 35mm (EN60715)
Operating Temperature -40/+85°C
Protection Rating IP20
Housing Material Thermoplastic UL94-V0
Standards of Compliance
IEC 61643-11 ,
EN61643-11,
UL1449 ed
Any orders below £75 subject to £6.00 carriage
- Stock: Out Of Stock
- Model: NIGSA23-415
- SKU: NIGSA23-415
- MPN: SA23-415